Afundamentos de tensão na presença de geração distribuída
dc.contributor.advisor | Leborgne, Roberto Chouhy | pt_BR |
dc.contributor.author | Silva, Carlos Vinicius Machado | pt_BR |
dc.date.accessioned | 2015-01-22T02:15:15Z | pt_BR |
dc.date.issued | 2014 | pt_BR |
dc.identifier.uri | http://hdl.handle.net/10183/109163 | pt_BR |
dc.description.abstract | A inserção de fontes de geração distribuída (GD) traz a possibilidade de diversificação da matriz energética e a redução de perdas elétricas no transporte de EE – porque as fontes localizam-se próximas aos clientes finais. Entre elas destacam-se as fontes fotovoltaicas, eólicas, pequenas centrais hidrelétricas (PCH) e termelétricas à biomassa. As duas primeiras, apresentam a peculiaridade de normalmente serem conectadas à rede através de inversores de frequência. As outras duas costumam ser conectadas diretamente ao sistema. Todavia, a GD também propicia consequências ao SEP, muitas vezes indesejadas, como variações nos parâmetros da qualidade da energia elétrica (QEE). O compromisso que se deve manter com a QEE entregue aos consumidores é de vital importância para as empresas transmissoras e distribuidoras de energia elétrica, bem como para os utilitários dessa EE. Além disso, para que haja o correto funcionamento de equipamentos eletrônicos e de diversos processos industriais é necessário que a energia elétrica permaneça em uma faixa de tensão aceitável. Entre os fenômenos de interesse da área de qualidade de energia elétrica, os quais devem ser eliminados ou mitigados para a melhor operabilidade do SIN, pode-se citar: harmônicos, flutuação de tensão, subtensão, sobretensão e afundamentos de tensão. Devido a observabilidade rotineira e aos prejuízos (financeiros e/ou técnicos) associados ao fenômeno, o interesse desse estudo consiste nos afundamentos de tensão. Nesse contexto, apresenta-se uma proposta para análise dos afundamentos de tensão em um ambiente com geração distribuída (fotovoltaica, eólica, PCH e termelétrica à biomassa) através de simulações de curtos-circuitos. Os resultados obtidos através da metodologia proposta mostram que a inserção de GD pode trazer uma variação no número de afundamentos de tensão e melhorar os níveis de tensão nas barras, sobretudo nos locais onde foram inseridas bem como em suas proximidades. Também, há redução no número de afundamentos de maior severidade os quais causam mais prejuízos e preocupação a operabilidade do SEP. | pt_BR |
dc.description.abstract | The insertion of distributed generation (DG) sources brings the possibility of diversification of energy sources types and the reduction of electrical losses in the transport of EE - because the sources are located close to end users. Among these sources are photovoltaic, wind, small hydropower and biomass-fired power plants. The first two, are usually connected to the network through frequency inverters. The other two are usually connected directly to the system. However, DG also provides consequences to the electrical power system, often unwanted, such as variations in the parameters of power quality (PQ). The commitment should be retained with the power quality delivered to customers. Moreover, for the correct operation of electronic equipment and various industrial processes it is necessary that the voltage remains within an acceptable range. Among the phenomena of interest to electric power quality, which must be eliminated or mitigated, we can mention: harmonics, voltage fluctuation, undervoltage, overvoltage and voltage sags (dips). Due to losses (financial and/or technical) associated with the phenomenon, the interest of this study consists of the voltage sags. In this context, we present a proposal for analysis of voltage sags in an environment with distributed generation (photovoltaic, wind, thermal and biomass-fired power plants) through simulations of short circuits. The results obtained through the proposed methodology shows that the inclusion of DG can bring a change in the number of voltage sags and improve voltage levels in bars, especially in places where they were inserted and in its vicinity. Also, there is a reduction in the number of severe voltage sags which cause more harm and concern to end-users and utilities. | en |
dc.format.mimetype | application/pdf | |
dc.language.iso | por | pt_BR |
dc.rights | Open Access | en |
dc.subject | Voltage sags | en |
dc.subject | Energia elétrica : Geração | pt_BR |
dc.subject | Energia elétrica : Distribuição | pt_BR |
dc.subject | Voltage dips | en |
dc.subject | Distributed generation | en |
dc.subject | Sistema elétrico de potência | pt_BR |
dc.subject | Power quality | en |
dc.title | Afundamentos de tensão na presença de geração distribuída | pt_BR |
dc.type | Dissertação | pt_BR |
dc.identifier.nrb | 000949606 | pt_BR |
dc.degree.grantor | Universidade Federal do Rio Grande do Sul | pt_BR |
dc.degree.department | Escola de Engenharia | pt_BR |
dc.degree.program | Programa de Pós-Graduação em Engenharia Elétrica | pt_BR |
dc.degree.local | Porto Alegre, BR-RS | pt_BR |
dc.degree.date | 2014 | pt_BR |
dc.degree.level | mestrado | pt_BR |
Este item está licenciado na Creative Commons License
-
Engenharias (7425)Engenharia Elétrica (462)